10kVA Dual Voltage UPS 200V (RACK/TOWER)

XPRT 10kVA Dual Voltage Online UPS

UPS power protection with dual voltage output for critical network electronics

These true online, double conversion UPS systems provide more capacity in less space. The XPRT-6kVA (4U) and XPRT-10kVA (6U) models save space, weight, and
power through a dual inverter design which provides selectable output voltages of 208/120V, 240/120V, 230/115V, or 200/100V without the need for transformers.

  • The Double Conversion Online technology, protects attached critical equipment by providing stabilization and power conditioning to incoming electrical power.
  • Dual inverter design which provides selectable output voltages of 208/120V, 240/120V,230/115V, or 200/100V without the need for transformers.
  • Peace of mind by protection for critical equipment from daily incoming electrical surges up to 800 Joules.
  • Purchase with confidence!  The XPRT 6kVA Redundant UPS is backed by an industry leading 3-year product warranty and a $50,000 Load Protection Policy.
  • For product configuration support and quotations please contact us via Chat, Phone or email at sales@republicpowersystems.com  
SKU: 90000014-1 Categories: ,

Product description

Features of the XPRT 10kVA Dual Voltage Online UPS include:

The XPRT 10kVA Dual Voltage Online UPS offers enhanced power protection for critical sensitive electronics.   These true online, double conversion UPS systems provide more capacity in less space.  The XPRT 10kVA save space, weight, and power through a dual inverter design.  This feature provides selectable output voltages without the need for step down transformers.

The XPRT 10kVA features hardwired input and output terminals and an optional output receptacle module. It includes one internal power module and two internal battery modules. The chassis contains a bypass switch which allows all modules to be removed without powering down the connected load.

  • POWER CAPACITY: 10kVA / 10000 VA / 8000 Watt capacity                            CLICK HERE TO CALCULATE YOUR BACKUP POWER REQUIREMENTS 
  • INPUT VOLTAGE: 100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220)VAC
  • INPUT CONNECTION: Hardwire10kVA dual voltage UPS rear
  • RUN TIMES: 5min. @ 100% full load, 16min. @ 50%
  • SCALABLE: Optional Extended battery run-times (up to 65min @ 100% and 194 min. @ 50% with 4x external battery packs)
  • OUTPUT VOLTAGE: 208/120VAC, 240/120VAC auto-sensing; 230/115VAC, 200/100VAC selectable
  • OUTPUT OUTLETS: Integrated bypass/PDU with hardwired or receptacle options
  • UPS TOPOLOGY: Double Conversion Online
  • PARALLEL CONFIGURATION: Up to three XPRT 10kVA units can be connected in parallel to provide up to 30kVA of backup power
  • COMMUNICATIONS INTERFACE: RS-232 and EBP (SNMP optional)
  • CERTIFICATIONS: UL, cUL, FCC
  • WARRANTY: 3 years electronics, 3 years battery warranty, optional 5 year warranty available (USA and Canada)
  • OPTIONS: PDUs, parallel tie/bypass panel options available

Benefits of the XPRT 10kVA UPS include:

Reduce power consumption and increase end to end efficiency with this powerful single-phase uninterruptible power supply.  Designed for high density critical loads, the XPRT delivers industry leading reliability, efficiency and flexibility. Output voltage and frequency are programmable to meet a wide range of US and international requirements.  XPRT has a high capacity internal charger model available for connection to matching external battery packs or large external battery systems.

HIGHLY CONFIGURABLE Hardwired input and output with terminal block connections or optional input cord and output receptacles

LONGER RUN TIMES Modular battery packs are available for extended battery runtimes

DUAL VOLTAGE OUTPUT Supports mixed voltage loads and plug types

HOT SWAPPABLE UPS Integrated maintenance bypass allows UPS electronics and battery to be serviced or replaced without interruption to critical load

$50,000 LOAD PROTECTION POLICY Offers protection against damaged connected equipment

MULTIPLE COMMUNICATIONS CAPABILITY RS-232 and optional Web/SNMP network interface.

Power Protection offered by the XPRT 10kVA UPS:

  • Power conditions such as electrical surges and sags
  • Total loss of electrical power or hard power “re-boots”
  • Unstable incoming power caused from outdated or faulty electrical wiring and or power distribution equipment
  • Harmonic interference from neighboring “high power draw” equipment
  • Severe weather events such as lighting storms, ice and snow storms and downed power lines
  • Unstable power generation from local utilities or on-site generation

Click here to learn more about the TOP 10 POWER ISSUES and UPS power protection features

Wide Power Input

The XPRT 10000VA Dual Voltage UPS supports incoming wide AC power input. The automatic voltage regulator (AVR), protects the UPS and connected equipment from adverse voltage conditions. This wide AC input capability can offer sag and surge protection without engaging the backup batteries of the UPS. This will reduce the stress on connected critical equipment and extends the battery life of the UPS.

Double Conversion Topology

Double Conversion Technology

                                Double Conversion Technology

The XPRT 10kVA Dual Voltage UPS is a true online double conversion uninterruptible power supply.  Incoming AC utility power is fed to the UPS’ rectifier converting it from AC to DC power. The converted DC power routes to a battery charging circuit and to the inverter for conversion back to AC power. The resulting “double converted” electrical power is pure sine wave output providing near perfect electrical power for connected equipment.

To ensure 7/24 up time the double conversion UPS topology utilizes a static “bypass switch” within its circuity design. If the XPRT 10kVA UPS detects a system failure, audible alarms will sound as the bypass switch is engages. This routes power around the failed UPS and ensures critical load power to target equipment.  This very important feature allows for 100% up time for critical equipment during repair or module replacement.

In the event of total power failure, the UPS will power off the rectifier when the loss of power is detected. The UPS’ internal backup batteries will continue to supply DC power to the inverter. There is no transfer time as the transition to battery power is instantaneous. This feature provides true uninterruptible power to mission critical equipment.

Technical Specifications

More
Model

XPRT-10kVA

Rated Power Capacity (Apparent/Active)

10kVA (8kW)

Voltage Range

100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220)VAC*

Frequency Range

40–70Hz

Power factor

> 0.97

Input Connection

10 ft cord with L14–30P plug or hardwire

Rated Voltage (Output)

208/120VAC, 240/120VAC auto-sensing; 230/115VAC, 200/100VAC selectable

Rated Frequency

50/60Hz auto-sensing ± 5% or frequency converter

Efficiency (Maximum%)

> 92%

Crest factor

3:1 at full load

Overload Capacity

110% for 300 sec; 130% for 30 sec; 200% for 5 sec

Battery Type

(24) 9AH/288VDC

Battery quantity and size

(6) 12V 9AH

Typical Recharge Time (100%)

< 3 hours to 90%

Unit Size (HxWxD)

16.9 x 26.0 x 10.6 in (6U)

Unit Weight

309 lbs

Cord Length

6 ft, L5–30P

Output Connection

Integrated bypass/PDU with hardwired or receptacle options

Voltage Harmonic Distortion

< 5% with non-linear load
<3% with linear load

Wave Form Type

Pure sine wave, zero transfer time

Operating Temperature

32–104°F (0–40°C)

Acoustic Noise

< 55dBA

Operating Elevation

11,500 ft above sea level

Certification

UL, cUL, RoHS,CE, RoHS

Connection

RS-232, USB, EPO, intelligent slot for optional cards (Web/SNMP, Relay/dry contact, Modbus)

External Battery Module

P90-BP72

External Battery Module Size (HxWxD)

17.2 x 24.6 x 3.5 in

External Battery Module Weight

104.4 lbs

Warranty

3 years battery warranty (USA and Canada)
3 years electronics

Available Options

parallel tie/bypass panel options available
PDUs

Weight309 lbs
Dimensions33.9 × 22.4 × 15.8 in

Estimated Run-Time

Battery Run Time Graph