How To Properly Maintain a UPS
Because of the critical role that the UPS provides, it is important that basic scheduled maintenance is performed to ensure optimal performance and protection capabilities of a UPS platform are in place and ready. This article will cover three basic areas of UPS maintenance, diagnostic testing, the overall UPS physical structure and the UPS battery itself. Due to the numerous applications and installed environments for UPS products, this article will only cover the recommended basics allowing the customer to assemble a maintenance schedule appropriate for their own unique operating environment.
DIAGNOSTICS
SANUPS UPS products have two forms of diagnostic capabilities. They are visual and audible alerts and software communications from the UPS. It is recommended to utilize both visual as well as software monitoring in the overall maintenance plan of a UPS.
Visual Inspection
- Unit is powered on, no unusual noises coming from unit or smells being emitted.
- No current alarm events, from front panel indicators or audible alarm.
- Battery load is optimal
- Battery Testing can also be manually be performed from the front panel or through software interface (Recommended every 6 months)
Software Monitoring
Utilizing SANUPS monitoring software, along with visual inspections will help to ensure system reliability for years to come. Depending on software and integrated hardware, multiple points of temperature and humidity can be monitored, power events detected and logged, and battery performance can be monitored. Events can be configured to trigger email alerts to designated employees. Additionally, this software provides automatic shut-down of target equipment, if utility power has not been restored before the UPS battery loses its remaining charge.
EXTERNAL INSPECTION
Due to a UPS’s size and weight, it is generally installed in the lower portion of a rackmount frame or directly mounted to the floor. Because of these mounting locations, visual inspection is vital to ensure continued operation. The potential for the intake of dirt & dust as well as physical damage is much higher in these lower mounting positions.
Air Intake and Exhaust
UPS BATTERY MAINTENANCE
Several aspects of a UPS battery must be known to ensure continued performance and maximized battery life for the UPS. The battery’s life can be affected by ambient operating temperatures, constant power “cycling”, operational wear and tear of the battery itself and how batteries are stored when not in operation. All issues must be taken into consideration when putting together a maintenance plan.
Ambient Operating Temperature
Internal and external VRLA batteries have a rated capacity based on an ambient temperature of 25°C (77°F). Operating the UPS and its batteries under these conditions will maximize the life of the UPS and result in optimal performance. While a UPS will continue to work in higher temperature ranges, it will result in diminishing battery performance and lifespan, as indicated in the chart below.
Ambient Operating Temperature | Battery Replacement Interval |
---|---|
25°C (77°F) | 4.5 years |
30°C (86°F) | 3 years |
35°C (95°F) | 2 years |
35°C (95°F) | 1.5 years |
Cycling
UPS Battery Maintenance
Battery Storage
When storing extra UPS batteries as there are a few important factors to consider when placing your UPS battery into storage or the UPS itself is not in use. Over time the batteries will self-discharge, it is recommended that batteries in long term storage be charged every 2 to 6 months depending on ambient storage temperature as indicated on the chart below:
Average Ambient Storage Temperature | Battery Re-Charge Interval |
---|---|
25°C (77°F) | Once every 6 months |
30°C (86°F) | Once every 6 months |
40°C (104°C) | Once every 2 months |
UPS MAINTENANCE CHECKLIST
Scheduled monitoring and maintenance of a UPS greatly reduces the chance of failure to supply power to connected critical equipment. In most cases daily simple observation is recommend both visually as well as monitoring through the SANUPS software. Listed below are the basics in developing a checklist and recommended intervals. Ultimately, end users will determine best practices for their operating environment. This checklist should be used as a guideline.
Visual Inspection
- Confirm ambient operating temperature and humidity are at target levels (Daily)
- Review UPS operational status (Daily)
- Front panel indicators are nominal
- No audible alarms coming from UPS unit
- No unusual noises or smells emitted from UPS
- Air Flow and exhaust (Weekly/Monthly/Quarterly depending on environment)
- Inspect, clean and or replace air filter media
- Verify proper airflow and exhaust are clear of obstructions as per operations manual
- Perform dusting and vacuuming of UPS and surrounding installed area
- Inspect external cabling (Monthly/Quarterly)
- Locked/positive connection to UPS
- Inspect for wear or signs damage to cabling structure.
- Inspect battery (6 months)
- Confirm integrity of battery enclosure, looking for swelling or damage
- Inspect/Clean battery terminals for corrosion
- Verify positive connection between cabling and battery terminals
- Replace batteries at recommended intervals
Diagnostics
- Review UPS operational logs power events, charge cycles and warning notifications (Weekly/Monthly)
- Run diagnostic battery tests (6 months)
- Off-Line load tests the UPS to ensure the system is entirely functional, return the system to following documented procedures in the user (Yearly)